ETC
ETC RSN-LV R2 Response 0-10V Gateway
- MPN:
- 4267A1102
- Availability:
- Usually ships within 2 business days when in stock.
Description
The ETC Response 0-10V Gateway accepts sACN or DMX control input and provides 24 channels of 0-10V sink control. It is ideal for both retrofit and new power-control system installations that use four-wire LED drivers and fluorescent ballasts. The Gateway also accepts a UL 924 Listed contact closure to set each channel’s output to a predetermined level for use in emergency systems.
Configuration of the 0-10V Gateway is simple with ETC’s Concert software for remote management or via the onboard four-button interface. Users can build their own custom dimming curve or take advantage of a pre-programmed curve in the Gateway’s library. The Gateway can be mounted anywhere standard DIN rail is installed. And ETC's variety of DIN rail enclosures ensure you have a secure, convenient place to house your DIN rail devices.
FEATURES
- Supports 24 0-10V control outputs, each supporting voltage sink connections up to 400mA maximum current per output
- 18-24VDC power input
- Supports streaming ACN (sACN) or DMX control input
- UL924 listed for use in emergency systems
- Remotely configurable via Concert
SPECIFICATIONS
FUNCTIONAL
- Supports sACN control input (ANSI E1.31)
- Supports USITT DMX512-A control input (ANSI E1.11)
- Supports 0–10V sink control (IEC60929 Annex E)
- Supports per-address- or per-universe-level priority
- Configurable dimming curve per channel
- Linear
- Mod-Square
- Custom
MECHANICAL
- Intuitive four-button interface
- Onboard display for identification, status and configuration
- Extruded aluminium enclosure
- Network and power activity indicators
- Blue power indicator
- Green and orange network activity indicator
- Female RJ45 for connection to lighting network
- Pluggable terminals provided for all wiring connections
- Selection switch for emergency input configuration
- Normally Open, Normally Closed or Off
- Trim pot for configuration of 0-10 V maximum voltage, +/- 1V
- 10 unit DIN enclosure
- Mounting complies with DIN43880 (35/7.5 rail)
ENVIRONMENTAL
- Ambient operating temperature: 0°–40° C (32°–104° F)
- Operating humidity: 5–95% non-condensing
- Storage temperature: -40°–70° C (-40°–158° F)
ELECTRICAL
- Compliant with IEEE 802.3i for 10BASE-T, 802.3u for 100BASE-TX
- 18-24 vDC power input using two-pin pluggable connection
- Maximum 18 W current draw at 18-24 V
- 24 0–10 V outputs, each supporting voltage sink connections, 400 mA maximum current per output
DMX INPUT PORT
- Optically-isolated input from the Gateway electronics
- Withstands fault voltages of up to 250 VAC
- Integrated DMX/RDM termination
CONFIGURATION
- Onboard configuration using intuitive four-button interface
- Configuration provided using Concert software
- Configurable starting address
- Up to four sources may be combined to the network with each source or address allowed an independent priority
PHYSICAL
- Dimensions (HxWxD): 1.22" x 6.55" x 4.13" (31 x 169 x 105 mm)
- Weight: 1.0 lbs. (0.45 kg)
- Shipping Weight: 1.5 lbs (0.68 kg)
REGULATORY AND COMPLIANCE
- cETLus Listed
- CE compliant
- EAC certified
- RoHS compliant
- WEEE
- UL 924 LISTED for emergency lighting applications